Page Title: CALIBRATING THE AQUA-GLO WATER DETECTOR (cont)
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM 10-6630-240-12&P TM 01461B-12&P/1 d. Connect  the  sampler  to  the  quick-release  valve  on  the  system.    The  three-way  valve  (1)  must  be  in  the  OFF position  (2)  before  attaching  the  sampler  to  the  remote  assembly:  the  valve  is  closed  or  off  when  the  valve  arm  is positioned approximately 45 degrees from the base of the valve .  (figure 2-26) Figure 2-26. WARNING The  Sampler  Valve  Hose  Assembly  must  be  properly  grounded  to  avoid  possible  fire  or explosion from static electrical charges.  An electrical continuity test of the ground hook-up should be performed prior to test to assure conductance of electrical charges from system to ground. e. Attach one end of ground wire (1) on any metal part of the  hose  assembly  (2)  and  the  other  end  to  a  ground. (figure 2-27) Figure 2-27 2-20