TM 10-5430-242-12&P
0009 00
Change 1
0009 00-6
Table 1. Operator Preventive Maintenance Checks and Services for
Fuel Storage Tank (continued).
ITEM
NO.
INTERVAL
MAN-
HOUR
ITEM TO BE
CHECKED OR
SERVICED
PROCEDURE
EQUIPMENT NOT
READY/
AVAILABLE IF:
16
During
Vent Fitting
Assembly (7)
Check relief cap, flame
arrestor, cap gasket, gasket,
and cam-lever arms for
evidence of leakage,
damage, or missing parts.
Check relief cap for
cleanliness and freedom of
operation. Check for
damaged or missing
gaskets.
Relief cap or flame
arrestor is
damaged or
missing. Relief
cap, gasket, flat
rubber gasket, or
cam-lever arms are
damaged or
missing.
17
During
Tank Drain Fitting
Assemblies (8)
Check immediate area for
evidence of leakage. Check
drain plug, drain hose, and
drain ball valve for damaged
or missing parts.
Drain plug, drain
hose, or drain ball
valve missing, not
properly connected,
or damaged.
18
During
Filler/Discharge
Assembly (9)
Check cam-lever arm and
elbow body for damage or
leakage.
Cam-lever arms
damaged or
missing. Elbow
body is cracked.
Elbow sealing
surface is badly
dented.
19
After
Tank (1)
Inspect for tears and
punctures. If torn or
punctured, perform
emergency repairs (WP
0006 00).
Tank has tears or
punctures that
cannot be repaired.
20
After
Filler/Discharge
Gate Valve (2) or
Ball Valve (3)
Check for bent or binding
stem or broken hardware.
Check gaskets and cam-
lever arms for damage.
Check for missing or
damaged dust caps and
plugs.
Stem, hand-wheel
or handle, gasket,
or cam-lever arms
are damaged or
missing. Dust caps
or plugs missing or
damaged.
21
After
Filler/Discharge
Hose Assembly
(4)
Check for cuts and tears.
Check fittings for distortion
and damage, or missing
gaskets, dust caps and
plugs.
Hose assembly is
damaged. Gaskets,
dust caps and
plugs are damaged
or missing.
22
After
Tank Drain Ball
Valve (5)
Check for bent or binding
stem, or broken handle.
Check for missing or
damaged dust caps and
plugs.
Stem or handle is
damaged or
missing. Dust caps
or plugs missing or
damaged.
|