TM 10-5430-242-12&P
0008 00
0008 00-5
Change 1
Check for cracked or broken flange adapter.
CORRECTIVE ACTION
Replace the cracked or damaged flange adapter.
See WP 0025 00 (GTA Model) or WP 0026 00 (Reliance and
MPC Models).
Check for loose or missing cap screws and washers.
CORRECTIVE ACTION
Replace the missing screws and washers. Torque the fastening
hardware to 15 or 16.0 ft-lb (20.34 or 21.70 N m). See WP 0025
00 (GTA Model) or WP 0026 00 (Reliance and MPC Models).
TROUBLESHOOTING PROCEDURE
RELIEF CAP AND FLAME ARRESTOR
SYMPTOM
Relief cap remains open.
MALFUNCTION
Check the relief cap for a broken or bent pivot pin.
CORRECTIVE ACTION
Replace the relief cap. WP 0025 00 (GTA Model) or
WP 0026 00 (Reliance and MPC Models).
Relief cap leaks.
CORRECTIVE ACTION
Replace the relief cap gasket. See WP 0025 00 (GTA Model)
or WP 0026 00 (Reliance and MPC Models).
SYMPTOM
Flame arrestor does not work properly.
MALFUNCTION
Check the flame arrestor for cracks, breaks, or wear.
CORRECTIVE ACTION
Service, repair, or replace the flame arrestor. See WP 0025 00
(GTA Model) or WP 0026 00 (Reliance and MPC Models).
|