TM 10-5430-242-12&P
0008 00
0008 00-1
Change 1 28 April 2002
OPERATOR AND UNIT MAINTENANCE
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANKS, FUEL STORAGE, 3,000,
10,000, 20,000, AND 50,000 GALLON
UNIT TROUBLESHOOTING PROCEDURES
INTRODUCTION TO UNIT TROUBLESHOOTING
This Troubleshooting Procedures chapter lists common malfunctions that may be found during the
operation or maintenance of the collapsible fabric fuel tank assembly or its components. Perform the
tests/inspections and corrective actions in the order listed in the table.
This manual cannot list all malfunctions that may occur, nor all tests or inspections and corrective actions.
If a malfunction is not listed or is not corrected by listed corrective actions, notify supervision.
WARNING
To prevent possible injury, read all warnings in the front of this
manual before performing troubleshooting.
TROUBLESHOOTING PROCEDURE
FILLER/DISCHARGE GATE VALVE ASSEMBLY (GTA MODELS)
SYMPTOM
Female coupling leaks.
MALFUNCTION
Check the female coupling for missing or loose cap screws, hex nuts, washers,
and lockwashers.
CORRECTIVE ACTION
Replace missing screws, nuts, washers, and lockwashers.
Torque the fastening hardware to 30 in-lb (3.41 N m). See WP
0020 00.
Check coupling and flange gaskets for damage or breaks.
CORRECTIVE ACTION
Remove the female coupling and replace the damaged gaskets.
Reinstall the female coupling. See WP 0020 00.
SYMPTOM
Male flanged adapter leaks.
MALFUNCTION
Check the male-flanged adapter for missing or loose hex-head cap screws, hex
nuts, washers, and lockwashers.
|