| |
TM 10-5430-242-12&P
0017 00
0017 00-1/2 blank
OPERATOR AND UNIT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)
COLLAPSIBLE FABRIC TANKS, FUEL STORAGE, 3,000,
10,000, 20,000, AND 50,000 GALLON
UNIT SERVICE UPON RECEIPT
SITE AND SHELTER REQUIREMENTS
Choose a site that is free from sharp objects (rocks, sticks, glass, etc.), which could cut or puncture the
tank. The site must not be subject to flooding or high water.
WARNING
If the tank is placed over drop-offs greater than 3.0 inches (7.62 cm), serious injury
to personnel or damage to the tank may occur.
The collapsible fabric fuel tank may be installed on a slope of up to 3 percent [3.0 inch (7.62 cm) rise in
100.0 foot (30.48 meters) run], but the tank base should not rest over abrupt drop-offs greater than 3.0
inches (7.62 cm).
SERVICE UPON RECEIPT OF MATERIEL
Inspect the equipment for damage incurred (punctures or tears) during shipment. If the equipment has
been damaged, report the damage in accordance with the instructions of DA PAM 738-750.
Check the equipment against the packing slip to see if the shipment is complete. Report all discrepancies
in accordance with the instructions of DA PAM 738-750.
Inspect Emergency repair items (sealing clamps, plugs, gaskets, and preformed packing) that are
packaged separately. Place the items in a secure storage area until required.
Check to see whether the equipment has been modified.
INSTALLATION INSTRUCTIONS
Refer to WP 0005 00.
PRELIMINARY SERVICING AND ADJUSTMENT OF EQUIPMENT
No preliminary servicing or adjustment is required.
END OF WORK PACKAGE
|