TM 10-4930-250-13&P
1.
Install inlet wye (2), suction hoses (8), and discharge hose (9) on pump-engine module.
m. Connect cables W201 (5) and W202 (6) to engine module (7).
n.
Install air cleaner IAW para. 2.4aa and acoustic cover (if provided) IAW para. 2.4ai on engine module.
o.
Open all inlet and outlet unisex coupling valves.
p.
Start system IAW para. 2.5e.
2.8.3
REPLACE ACCESSORY MODULE.
(Refer to figure 2-27.)
WARNING
Serious injury could occur if heavy equipment is moved/lifted without sufficient personnel to do the
job.
Always use four personnel to move or relocate the pump-engine module. Use proper physical
lifting procedures or use a suitable lifting device or dolly. Wear safety shoes, gloves, and other
suitable protective clothing.
a.
Shut down system IAW para. 2.5. 1.
b.
Disconnect cables W201 (5) and W202 (6) from engine module (7).
Stow cables in accessory module (4).
c.
Remove air cleaner from engine and install dust cap on intake manifold IAW with para. 2.9m. Stow air cleaner in
accessory module (4).
d.
Remove accessory module (4) and position replacement accessory module for connection to system.
e.
Connect cables W201 (5) and W202 (6) to engine module (7).
f
Remove air cleaner from accessory module and install on engine IAW para. 2.4aa.
g.
Start system IAW para. 2.5e.
2.8.4
Re0ace Liouid Fuel Filter-Separator.
(Refer to figure 2-27.)
WARNING
Serious injury could occur if heavy equipment is moved/lifted without sufficient personnel to do the
job. Always use four personnel to move or relocate the pump-engine module, liquid fuel filter-
separator, and accessory module. Use proper physical lifting procedures or use a suitable lifting
device or dolly. Wear safety shoes, gloves, and other suitable protective clothing.
a.
Shut down system IAW para. 2.5. 1.
b.
Defuel liquid fuel filter-separator (11) IAW paragraph 2.7.d.
c.
Disconnect 6' hose (9) from the inlet port.
d.
Disconnect recirculation manifold (12) from the outlet port.
e.
Remove liquid fuel filter-separator (11) and position replacement liquid fuel filter-separator for connection to system.
I.
Install recirculation manifold (12) on outlet port.
g.
Connect 6' hose (9) to the inlet port.
It.
Open manual vent valve while liquid fuel filter-separator (11) is flooding. Close vent at first appearance of fuel.
i.
Start system IAW para. 2.5e.
2.8.5
Replace Any Hose or Fitting.
a.
Close valves to isolate hose or fitting.
b.
Remove hose or fitting from system and drain into a suitable container.
c.
Install replacement hose or fitting and open valves.
d.
Continue mission.
2-40
|