TM 10-4930-247-13&P
4-13. (MODEL HTARS100) SINGLE POINT REFUELING NOZZLE (D1) ASSEMBLY REPAIR - cont.
(8)
Remove self locking nut (15), flat washer (16), screw (17), and flat washer (18) from collar (24).
(9)
Remove handle (23) from collar (24).
(10)
Slide cap (19) off of handle (23).
NOTE
Old grip must be cut from handle. Do not remove unless defective.
(11)
Place handle (23) in vi se.
(12)
Remove self locking socket screw (20) and flat washer (21) from inside grip (22).
(13)
Cut grip (22) from handle (23).
(14)
Repeat steps (8) through (13), except step (11), for other handle.
b.
Cleaning.
WARNING
Dry cleaning solvent, P-D-680, TYPE III, is potentially dangerous to personnel and
property. Eye and skin protection is required. Avoid repeated and prolonged skin
contact. Wash hands immediately after exposure. Do not use near open flame or
excessive heat. Use only in areas with good ventilation.
Using wiping rags and cleaning solvent, remove dirt and contaminants from all components.
c.
Inspection. Refer to figure 4-1.
(1)
Inspect inlet elbow (13) for cracks and corrosion. Check for scratches and abrasion at all sealing surfaces.
(2)
Inspect body (14) for cracks, corrosion and damaged or missing parts.
(3)
Inspect coupling adapter (5) for cracks, missing components and corrosion.
(4)
Inspect collar (24) for cracks and corrosion.
d.
Repair. Replace damaged or defective components. Replace all mandatory replacement parts. Repair non-
valved dry break coupling on coupling adapter (para 4-14).
e.
Assembly. Refer to figure 4-1.
NOTE
Ensure that all parts identified as mandatory replacement parts are discarded and
replaced with new components.
(1)
Place handle (23) in vise.
4-10 Change 4
|