TM 10-4930-243-13&P
4-11. GFA REPAIR.
This task consists of:
a.
Disassembly
b.
Repair
c.
Assembly
INITIAL SETUP:
Tools:
General Safety Requirements:
Tool Kit, General Mechanics (Item 1, Appendix B)
Crimping Tool (Item 2, Appendix B)
WARNINGS
Fuels are toxic and flammable. Do not get on person or
Equipment Condition:
clothing. Do not use near open flame.
GFA Nozzle removed from CCR Nozzle
Area should be well-ventilated.
(refer to system T.M.)
Using dry cleaning solvents incorrectly can cause injury
or even death.
Fuels Flammable No Smoking
a.
Disassembly
NOTE
The dust cap assembly should not be removed from the nozzle body unless replacement is required.
(1)
Remove dust cap (1) from inlet end of body (5).
(2)
Remove plug (2) from discharge end of body (5).
(3)
Push cables (3) through handle of body (5) to expose the crimp fitting (4) on end of cables.
(4)
Cut cables (3) to remove crimp (4)
(5)
Pull cables (3) back through handle of the body.
b.
Repair. Replace defective parts.
c.
Assembly
(1)
Insert the two loose ends of cable (3) through the hole in the handle of body (5) from right to left.
NOTE
Ends of cable should not protrude more than 1/8 in past end of crimp before crimping.
(2)
Insert the two loose ends of cable (3) through crimp fitting (4) and crimp the fitting
(3)
Pull cables (3) back through body (5) until crimp fitting (4) rests against inside lip side of body (5).
(4)
Install plug (2) over outlet end of body (5).
(5)
Install cap (1) into inlet end of body (5).
4-14
|