TM 10-4930-243-13&P
4-10. CCR NOZZLE ASSEMBLY REPAIR
This task consists of:
a.
Disassembly
b.
Repair
c.
Assembly
INITIAL SETUP:
Tools:
Equipment Condition:
Tool kit, General Mechanics (Item 1, Appendix B)
CCR Nozzle removed from fuel system.
Vise (Item 2, Appendix B)
(Reference Applicable System TM)
General Safety Requirements:
Materials/Parts Required:
Solvent (Item 1, Appendix E)
WARNINGS
Wiping Rag (Item 2, Appendix E)
Fuels are toxic and flammable. Do not get on
Silicone Compound (Item 3, Appendix E)
person or clothing. Do not use near open flame.
Sealing Compound (Item 4, Appendix E)
Area should be well-ventilated.
Packing. Preformed (Item 1, Appendix G)
Using dry cleaning solvents incorrectly can
cause injury or even death.
Fuels Flammable/No Smoking
a.
Disassembly.
(1)
Pull the nozzle collar (1) back to release the cap (2) from the discharge end of the nozzle. Remove the
cap assembly (2).
(2)
Remove screw (3) holding the ground cable assembly (4) and cap assembly cable (2) to the nozzle
housing (5).
(3)
Remove strainer body (6) with coupling assembly (10) attached, by hand from strainer housing (7).
(4)
Remove strainer (8) and preformed packing (9) from strainer housing (7). Discard packing.
(5)
Place strainer body (6) into a soft face vise.
(6)
Unscrew coupling assembly (10) from strainer body (6).
(7)
Remove plug (11) from coupling half (13).
(8)
Remove gasket (12) from coupling half (13).
4-10
|