TM 10-4930-241-13
2-18. OPERATING PROCEDURES - Cont.
(1)
Defuel Mode - Valve Section to Fill Side of Fuel Tanks. Refer to figure 2-31.
WARNING
Do not touch surfaces with bare skin. Bare skin will freeze to metal
surfaces in subzero temperatures. Always wear arctic mittens when
handling components
NOTES
Handwheel on valve sections may be opened to allow fuel from
one or two supply tankers at the same time. Open handwheels
as needed to support your mission.
Handwheels on fueling manifolds may be opened to allow fuel
flow to fill one, two or three fuel tanks at the same time. Open
valves as needed to support your mission requirements.
The following procedures describes filling three fuel tanks at the
same time from a supply tanker.
(a) Connect valve section (1) to supply tanker.
(b) Ensure valve section (3) is closed.
(c) Turn handwheel (2) to open position on valve section.
(d) Ensure gate valve (4) on fueling manifold is closed.
(e) Turn handwheel (5) to open position on valve section.
(f)
Ensure valve section (6) is closed.
(g) Turn handwheels (7, 8 and 9) to open position on fueling manifolds.
(h) Ensure gate valves (10, 11 and 12) are closed.
(i)
Start and operate primary 600 GPM primary pump (13) until operation is complete.
(j)
Shutdown 600 GPM primary pump (13).
(k) Close all valves.
(l)
Disconnect valve section ( 1 ) from supply tanker.
2-74
|