TM 10-4930-241-13
2-18. OPERATING PROCEDURES - CONT.
(10)
Refuel Mode - Fuel Tank. Secondary 600 GPM Pump and 200 GPM Filter-Separator Bypass. Refer
to figure 2-40.
WARNING
Do not touch surfaces with bare skin. Bare skin will freeze to metal
surfaces in subzero temperatures. Always wear arctic mittens when
handling components.
(a) Connect valve section (1) to supply tanker and open valve.
(b) Ensure valves (2 and 3) are closed.
(c) Open valve (4).
(d) Ensure valves 5, 6, and 7) are closed.
(e) Open valves (8 and 9).
(f)
Ensure valve (10) is closed.
(g) Start and operate secondary 600 GPM pump (11).
(h) When operation is complete, shut down 600 GPM pump (11)
(j)
Close all valves.
2-88
|