TM 10-4930-232-12&P
Leakage Definitions:
Class I
Seepage of fluid (as indicated by wetness or discoloration) not great enough to form drops.
Class II
Leakage of fluid great enough to form drops but not enough to cause drops to drip from
item being checked/inspected.
Class III
Leakage of fluid great enough to form drops that fall from the item being
checked/inspected.
Table 2-1. Operator Preventive Maintenance Checks and Services (PMCS).
NOTE
Within designated interval, the checks are to be performed in the order listed.
Item
Interval
Item to Be
Procedure
Not Fully Mission
No.
Checked or
If:
Serviced
1
Before
Gate valves
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged
able.
2
Before
Wye and tee assemblies
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged
able.
3
Before
Couplings
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged
able.
4
Before
Hoses
Check for breaks, cracks, dete-
Hose(s) unserviceable
rioration or damage.
5
Before
Quick-acting valves
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged
able.
6
Before
Collapsible tanks
Refer to PMCS in applicable
technical manual.
7
Before
Filter/separators
Refer to PMCS in applicable
technical manual.
8
Before
Pumps
Refer to PMCS in applicable
technical manual.
9
Before
Nozzles
Refer to PMCS in applicable
technical manual.
10
During
Gate valves
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged
able.
11
During
Wye and tee assemblies
Check for leaks at seal, gasket
Leaks are observed or
or fittings. Hardware missing or
hardware is unservice-
damaged.
able.
12
During
Hoses
Check for breaks, cracks,
Hose(s) unservicable
deterioration or damage.
Change 2 2-3
|