TM10-4330-235-13&P
4-9. REPLACE SIGHT GAGE
This task covers:
a. Removal
b. Installation
INITIAL SETUP
Tools
General Mechanic Tool Kit (Appendix B, Section Ill, Item 4)
Materials/Parts
Gasket (Appendix H, Item 5)
Equipment Conditions
System Shut Down
General Safety Instructions
WARNING
Do not smoke within 50 feet (15.34 meters) of filter/separator.
REMOVAL
a. Provide a suitable container to receive fuel and open manual drain valve (1) to drain contents of
filter/separator below level of sight gage.
b. Open air valve (2) to vent vessel.
c. Remove screws (3) and flat washers
float ball (6).
d. Remove gasket (7).
(4). Pull gage body (5) from mount on filter/separator and remove
INSTALLATION
a. Place float ball (6) in gage body (5) and position gage body and gasket (7) on filter/separator.
b. Secure body in place with screws (3) and flat washers (4). Tighten screws snugly.
c. Close vent valve (2) and drain valve (1).
4-10
|