TM 10-4320-347-13&P
2.12. PREPARATION FOR MOVEMENT . For general preparation of the pump assembly for
movement, perform the following steps (Refer to Figure 2-3).
a.
Disconnect slave connector (21) from the 24 volt direct current power supply and place dust cap
(20) onto slave connector.
NOTE
Always drain fuel into an appropriate container. Dispose of
collected fuel per local standard operating procedures.
b.
Drain all fuel from all suction and discharge hoses.
c.
Remove nozzle assembly (18) from discharge hose assembly (16). Connect dust cap (15) onto the
discharge hose assembly and the dust plug (17) into the nozzle assembly.
d.
Remove discharge hose assembly (14) from the pump discharge male coupling (12). Connect dust
cap (11) onto pump discharge male coupling and dust plug (13) into to discharge hose assembly.
e.
Remove suction strainer (10) from suction hose assembly (9). Connect dust plug (8) into suction
hose assembly.
f.
Remove suction hose assembly (7) from pump female suction coupling (5). Connect dust cap (6)
onto suction hose assembly (7) and connect dust plug (4) into pump female suction coupling (5).
g.
Remove grounding cable (2) from pump (3) and ground rod assembly (1).
h.
Drain fuel from pump housing by opening drain cock (22) on side of pump.
2.13. DECALS AND INSTRUCTION PLATES . To assist the operator in the use of the pump assembly,
various decals and information plates have been placed on the unit. The location of each of these decals
or instruction plates and the wording of each one is shown in Figure 2-6.
Figure 2-6. Decals and Instruction Plates.
2-15
|