TM 10-4320-342-24
2-89.
STUD TERMINAL (GROUND) REPLACEMENT.
This Task Covers
a. Removal
b. Service
c. Installation
INITIAL SETUP
Tools
Equipment Condition
General Mechanics Tool Kit (App B, Sect III,
Ground Wire disconnected (System TM)
Item 1)
200/600 GPM Pump shut down (Para 2-7c,
TM 10-4320-342-10)
Materials/Parts
Lockwasher (App F, Item 64)
Self-locking Nut (App F, Item 106)
a. REMOVAL. Refer to Figure 2-119.
(1)
Open door (1).
(2)
Remove self-locking nut (2), lockwasher (3), wiring (4) and lockwasher (5) from ground terminal (6).
(3)
Remove ground terminal (6) from 200/600 GPM (7).
b. INSTALLATION.
WARNING
Improper grounding (bonding) connections between wiring, frame and ground
terminal can generate a static discharge (spark). Make sure connections provide a
metal-to-metal contact between wiring, frame and ground terminal. A static
discharge could ignite fuel or cause an explosion of fuel vapor and cause
personnel injury or death.
(1)
Install ground terminal (6) on 200/600 GPM pump (7).
(2)
Install lockwasher (5), wiring (4), lockwasher (3) and self-locking nut (2) on ground terminal (6).
(3)
Close door (1).
2-268
|