TM 10-4320-324-14
(16)
Perform during operation PMCS (Table 2-1).
CAUTION
Ensure discharge valve is open. Pump can
overheat if discharge valve is closed for long
periods of time. A vapor-locked condition may
result. If this occurs, shut down engine and
allow pump to cool before filling housing with
liquid.
b.
Run. During normal operation the pump assembly
should run without further intervention. Make periodic
checks of
all valves, gauges and indicators. If a
malfunction is indicated, shut down pump at once.
c.
Shutdown.
CAUTION
Do not shut engine down suddenly from full
speed unless an emergency exists. Allow engine
to stabilize at idle before shutdown.
(1)
Push and raise throttle control (5) from detent to
set engine speed to idle.
(2)
After approximately two minutes, close discharge valve (3) and suction valve (2).
(3)
Push in EMERGENCY STOP switch (6).
(4)
Perform after operation PMCS (Table 2-1).
2-15
|