TM 10-3835-231-13
Table 4-1. Unit Preventive Maintenance Checks and Services for Tactical Petroleum Terminal
Location
Item
Interval
Item to Check/Service
Procedure
Not Fully Mission Capable if:
No.
1
Daily
Pressure Regulator
a. Place a container under the
Drain inoperable.
Strainers
SEDIMENT TRAP DRAIN and
open the valve to dump excess
debris from the bottom of sediment
trap.
b. Check the condition of the fluid
Fluid excessively dirty.
upstream of the WYE Strainer by
placing a container under the AIR
BLEED valve outlet and collecting a
small amount of fluid. If the fluid
appears dirty the WYE Strainer
must be cleaned.
NOTE
If
WYE
Strainer
needs
frequent cleaning or the
response time of the main
pressure regulator cylinder
valve starts to slow down
the integral strainer in the
needle valve should also be
cleaned.
2
Weekly
Complete System
Check for leaks.
Leak found.
3
Weekly
Grounding System
Check for broken ground cables or
Any damage that would not
damaged ground rods.
allow a good ground.
4-49
|