T M 1 0 - 3 8 3 5 - 2 1 9 - 14
b. Attaching Discharge Hoseline to Pump Assembly. (figure 2-6)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(15)
(14)
Open chest containing hoseline flow control kit.
Remove one coupling half quick disconnect (female) (1).
Remove one grooved to external thread coupling (2).
Wrap one layer of white teflon tape (3) on threads of grooved-to-external (2) and attach coupling to
quick disconnect coupling half (1). Coupling must be tight to prevent leakage.
Slide pipe coupling clamp rubber gasket (4) over end of hoseline (5). Make certain gasket is flush with
e n d.
Place coupling (2) in line with hoseline (5) and slide gasket (4) over joint. Center gasket in place.
Position lower pipe coupling half (6) over gasket, then position upper pipe coupling clamp half (7).
Install two bolts (8) and nuts (9) so that nuts (9) will be exposed on the upper coupling half (7).
Hand tighten nuts (9) evenly, then with wrench, tighten nuts evenly until coupling faces meet.
Continue tightening nuts (9) evenly until both bolts (8) are secure.
Remove caps (10) from pump discharge ports.
Ensure that gasket is properly positioned in hoseline quick disconnect coupling half.
Attach assembled hoseline (5) to pump discharge port and secure with camlock levers (11).
Repeat steps 1 through 13 if a second hoseline is required.
2 - 2 3
|