TM 10-6630-240-12&P TM 01461B-12&P/1 f. Flush the inlet hose by turning the three-way valve (1) to the FLUSH position: the valve arm is horizontal to the base of the valve (2).  Pass at least 3.2 quarts (3 or more liters) into a 5 gallon receptacle to remove contaminants from the inlet valve.  (figure 2 - 27) Figure 2-27 g. Take  a  sample  by  holding  the  sampler  upright  and  turn  the  three-way  valve  (1)  to  the  test  position.    Collect enough fuel to fill the PVC sample bottle - no more than 1 quart.  (figure 2-28) Figure 2-28 h. Allow 500 milliliters (17 ounces) or less of fuel to pass through the assembly and free-water test pad.  Record sample volume for reporting. 2-21