Page Title: CALIBRATING THE AQUA-GLO WATER DETECTOR (cont)
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM 10-6630-240-12&P TM 01461B-12&P/1 e. Depress the switch button on the instrument pack and read the calibration meter: if the meter reads "0", the water detector  calibration  procedure  is  complete  (Figure  2.25).    If  the  meter  reads  any  increment  other  than  "0",  you  must adjust the internal calibration screw until the water detector is "zeroed-out" (i.e., the meter lever shaft reads "0").  See f., g., and h.  below for instructions.  Also refer to the calibration card stored with kit.  (figure 2-21) Figure 2-21 2-16