TM 10-3835-231-13 e. Fuel Test Procedure. (1) Adjust valves so that fuel can be pumped through the section being tested to exhausting air. (2) Slowly  pump  fuel  into  the  system,  not   to  exceed  a  flow  rate  of  200  gpm.    When  all  air  is  evacuated, discharge valves should be closed, the section should be filled with fuel and the pump should be stopped. (3) Check all connections for leaks. (4) Start the pump and raise pressure to 25 psi, stop the pump, check for leaks, and check gauges. (5) If no leaks are found and gauges are okay, start pump and raise pressure to selected test pressure. (6) Stop  pump,  check  for  leaks,  and  hold  the  test  pressures  for  a  period  long  enough  to  inspect   the  entire system under test. (7) If leaks are found, relieve pressure, drain leaking section, and make repairs, adjustments, or replacements as necessary.  Retest after repairs are made. 4-47

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business